상수도 시스템 내에서의 실시간 수질감시를 위한 LPCF 모형의 적용 및 검증 |
---|
학술지명 J. Korean Soc. Environ. Eng.,
저자 김성수
발표일 2018-11-30
|
Currently, various water quality parameters are monitored for real-time contamination warning in the water supply system of South Korea. If the measured values of water quality parameters exceed the threshold, contamination warnings are issued. However, the U.S. environmental Protection Agency (EPA) reported the following limitations of the contamination warning system based on these thresholds. First, irregular and sudden hydraulic changes in water supply system caused by pump or valve malfunction may cause measurement error of the water quality sensors, which may cause nuisance and unnecessary false-positive alarms. Second, in the case of long-term outflow of micropollutants, water quality changes are slightly within the thresholds, which causes a serious monitoring error of false-negatives that cannot be detected even in actual contamination. Therefore, the U.S. EPA applied a linear prediction?correction filter (LPCF) model for real-time contamination warning, which is based on the autoregressive (AR) model. The main purpose of this study is to develop a contamination warning technique to be applied to water supply system of South Korea. For the development of a real-time contamination warning technique, the LPCF model was applied and Testing with water quality data collected from G_water supply system of South Korea. |