물 자연 그리고 사람 - 물로 더 행복한 세상을 만들어가겠습니다.
HOME성과논문실적

논문실적

In-line Inspection 기술을 활용한 대구경 용수공급관로 상태평가(S 광역상수도 사례연구) 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
In-line Inspection 기술을 활용한 대구경 용수공급관로 상태평가(S 광역상수도 사례연구)
학술지명 한국수처리학회 저자 김재학,김세원,배철호,김정현,신병호,구자용
발표일 2018-10-31

S multi-regional water supply system is a large-scale water supply facility with a capacity of 8.5 million m3/day, which is responsible for supplying clean and safe tap water to all consumers of the metropolitan area. Since the direct or indirect impact of a single pipeline accident is serious in the large-scale pipeline with a diameter of more than 2,000 mm, continuous and systematic management is necessary. In this study, some sections of the S2 bulk water supply pipelines with an age of more than 38 years, which were expected to be seriously deteriorated, were selected for diagnosis spot. In-line inspection with MFL(Magnetic Flux Leakage) sensors was applied in the field. Through the application of MFL, it was possible to accurately pinpoint vulnerable sections, which were difficult to distinguish by direct investigation of manpower. In addition, we could derive necessary items for efficient large-diameter MFL diagnosis and verified the reliability of MFL diagnosis method through a comparison of MFL diagnosis results and UT-test results. Currently, MFL has limitation to implement in severe ovality and it is expensive foreign high-tech equipment. If we can localize MFL technology and the reliability of this technique is gradually secured, MFL will play a very important role in decision-making process of pipeline rehabilitation in the future

목록