A STUDY ON THE PERFORMANCE CHANGE OF WATER TO AIR HEAT PUMP SYSTEM ASCCORDING TO THE HEAT EXCHANGE AMOUNT |
---|
학술지명 2017 ICCHMMT
저자 차상훈,조용,신영섭
발표일 2017-05-29
|
Since cop21, interest in renewable energy is growing rapidly. Together with that, raising the efficiency of renewable energy currently in use is also a topic. Therefore, in this study, As a way to increase efficiency, we analyzed the influence of the heat exchange amount on the performance of the water-water heat pump system. The Chungju Water Treatment Plant which is operated and managed by K-water was selected for the analysis target. The Chungju cooling / heating system consists of water-air heat pump, raw water pump, brine water pump, heat exchanger and indoor unit. The instruments, such as power meter, flowmeter, thermometer, were installed for data acquisition. Prior to the study, the Chungju simulation model was constructed by TRNSYS, and verified against operational data. For convenience of analysis, a program using Excel VBA was developed. Finally, the difference in COP between the COP at rated operation of the pump capacity used in the Chungju cooling / heating system and the optimal operation derived in this experiment was compared. The results of this study are expected to contribute to improving the efficiency of water-air heat pump system using raw water as a heat source |