물 자연 그리고 사람 - 물로 더 행복한 세상을 만들어가겠습니다.
HOME성과논문실적

논문실적

통계적 기법을 이용한 배급수 관망 내 감압밸브 성능 평가에 관한 사례 연구 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
통계적 기법을 이용한 배급수 관망 내 감압밸브 성능 평가에 관한 사례 연구
학술지명 대한상하수도학회 저자 박노석,윤석민,이영주,최두용
발표일 2015-09-25

It has been widely accepted that the pressure management of water distribution systems using pressure reducing valves(PRVs) would be an effective method for controlling leakages. A pressure reducing valve (PRV) regulates outlet pressure regardless of fluctuating flow and varying inlet pressure, thereby reducing leakage and mitigating the stress on the water distribution system. However, the operation of a PRV is vulnerable to its mechanical condition and hydraulic operability. In this research, the effect of PRVs installed in water distribution system are evaluated in terms of hydraulic pressure reduction and mechanical performance by analyzing measured pressure data with statistical approach. A statistical approach using the moving average filter and frequency analysis based on fourier transform is presented to detect abnormally operated PRVs that have been densely installed in water distribution system. The result shows that the proposed approach can be a good performance evaluation method by simply measuring pressures for the PRVs.

목록