물 자연 그리고 사람 - 물로 더 행복한 세상을 만들어가겠습니다.
HOME성과논문실적

논문실적

원수열원 히트펌프 축열시스템의 동절기 성능분석 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
원수열원 히트펌프 축열시스템의 동절기 성능분석
학술지명 한국신재생에너지학회 2011 춘계학술대회 저자 조용,이동근
발표일 2011-05-26

Performance of the raw water-source heat pump system with a thermal storage tank has been analyzed in winter season. The raw water is transferred through the multi-regional water supply system from Han river. Raw water is large temperature difference resource compared with groundwater. Although the raw water temperature drops to 0.6℃ due to the heavy snowfall and the severe cold in late January and early February, 2010, the system has been normally operated without any trouble this winter. The unit COP and system COP considered all pump power consumption were estimated based on the second-by-second data of the all sensors. The monthly averaged unit COP and system COP are 3.37 and 2.76 respectively with 1.4℃ of raw water in January, 3.55 and 2.89 with 1.6℃ raw water in February, 3.82 and 3.15 with 5.4℃ raw water in March. The performance of the system are increased with raw water temperature, and the COPs are higher than the water-to-air heat pump system using relatively high temperature raw water from Daecheong reservoir because the water-to-water system was operated on the full load condition and was stopped when the thermal storage tank was full of the high temperature water.

목록