정수장 내 수온차 히트펌프 성능 분석 |
---|
학술지명 대한설비공학회 2011 하계학술발표대회
저자 윤린,오선희,조용
발표일 2011-07-08
|
The dynamic characteristics of the raw-water heat pump system in the tap water-treatment facility are investigated over a year by using the TRNSYS. When the temperatures of the rooms are under the control to 22℃ and 25℃ in the heating and cooling season, the average COP from the simulator shows 2.85 and 6.2, respectively. The seasonal power consumption, COP, cooling and heating rate from the TRNSYS show the similar trends and values to the experimental results. |