물 자연 그리고 사람 - 물로 더 행복한 세상을 만들어가겠습니다.
HOME성과논문실적

논문실적

유공벽을 이용한 우류식 염소접촉조 사류 저감방안 연구 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
유공벽을 이용한 우류식 염소접촉조 사류 저감방안 연구
학술지명 대한상하수도학회 저자 박현오,원찬희,김사동,박노석,차민환
발표일 2010-10-01

From the results of tracer test for the existing chlorine contactor in Y water treatment plant, T10 and T10/T were calculated as 130 min and 0.16, respectively. Therefore it required the modification schemes for improving hydraulic efficiency, surrogated by T10 and T10/T, and disinfection performance. In this study, in order to reduce dead zone within contactor, to install porous baffles in the near of each corner was suggested and verified using transient CFD(Computational Fluid Dynamics) simulation technique and tracer tests on dynamic condition. From the results of simulation and tracer tests, it was revealed that porous baffles installed have been effective to reduce dead zone within contactor, and increase plug flow fraction.

목록