슈퍼마켓용 CO2/NH3 캐스케이드 시스템과 CO2 2단 시스템의 성능평가 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
슈퍼마켓용 CO2/NH3 캐스케이드 시스템과 CO2 2단 시스템의 성능평가
학술지명 대한설비공학회 하계학술대회 저자 조용,윤린
발표일 2010-06-25

Due to environmental concerns the natural refrigerants of CO2 and NH3 has been reintroduced as replacements of the chemical refrigerants of R404A in supermarket refrigeration. Possible system configurations for the natural refrigerants are the CO2-NH3 cascade system and the CO2 two-stage system. In this study, the comparison of the system performance between the CO2-NH3 cascade system and the three-different CO2 two-stage systems are conducted. The suction line heat exchanger and the internal heat exchanger are added to improve the performance of the CO2 two stage system. The COP of the cascade system is highest among the present simulated systems due to the improvement of the low stage system performance of the CO2 cycle.