물 자연 그리고 사람 - 물로 더 행복한 세상을 만들어가겠습니다.
HOME성과논문실적

논문실적

Characteristics of Pretreatment Parameters and Bubble Size Influencing Dissolved Air Flotation Efficiency 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
Characteristics of Pretreatment Parameters and Bubble Size Influencing Dissolved Air Flotation Efficiency
학술지명 IWA Flotation 2007 저자 손병용,민진희,안효원,권순범
발표일 2007-09-14

his study attempts to investigate the relationship between the size of flocs and the efficiency of a DAF method using a PDA (Photometric Dispersion Analyzer) developed by Gregory (2003) and Nelson that is used to monitor the floc generation through on-line access. This study applied an actual measurement to investigate how the size of PIA bubbles affects flotation velocity and introduced similar results as theoretical flotation velocity reported in other literatures. It was evident that the results play a role in the improvement of reliabilities for the evaluation of the flotation velocity of flocs-bubbles. In the results of the evaluation of the electro static characteristics for applying DAF treatments, the amount of coagulants was configured based on the zeta potential value that is to be controlled as +2~4 mV in order to improve the treatment efficiency. In the results of the coagulation intensity test using a PDA, the condition of 900 sec-1 for 1~3 sec demonstrated excellent treatment efficiencies in a DAF process. Also, in the results of the flocculation test based on the flocculation index, the condition of the locculation combination of 70/50 sec-1 showed reasonable results to operate DAF.

목록