물 자연 그리고 사람 - 물로 더 행복한 세상을 만들어가겠습니다.
HOME성과논문실적

논문실적

Identification and Prioritization of performance limiting factors for water treatment plant optimiza 게시글의 제목, 학술지명, 저자, 발행일, 작성내용을 보여줌
Identification and Prioritization of performance limiting factors for water treatment plant optimiza
학술지명 IWA 저자 안효원,문용택,김정현,박노석,배철호
발표일 2006-06-30

Performance limiting factors (PLFs) derived from 161 drinking water treatment plants 
(DWTPs), assessed by the lnternational Technical Diagnosis and Assistance Center. were
 analyzed and evaluated in this study. In order to conduct research, 161 DWTPs were 
divided into five categories depending on their capacity, and into twelve groups 
According to processes and facilities. From the results of analyses, PLFs and their 
distribution ratio derived from each category were significantly different. Filtration 
was the most important performance limiting factor in all DWTPs of five categories, and
 PLFs in filtration were backwashing velocity, media configuration, bed depth, and 
formation of mud-ball. The PLFs in coagulation-flocculation process were found to be 
coagulant dose, mixing intensity, mechanical problems, and others in the order of 
frequency of occurrence. Also, insufficient disinfection ability, is resulting from 
insufficient hydraulic detention time, improper chlorine dose and injection point, is 
the most significant among PLFs in a clear well. In the case of sedimentation, 
inappropriate baffle structure and excessive upward velocity were PLFs. In addition, 
the results showed that high turbid water and low alkalinity in rainy season, ferric 
and manganese ions, and ammonia nitrogen have contributed significantly to the 
performance of DWTPs.

목록